Field & Lab AC Dielectric Test Sets

Mobile 6CP/6CB AC Hipot Series

The 6CP/6CB line is designed for dielectric strength testing of a wide range of electrical equipment such as medium and low voltage switchgear, circuit breakers, transformers, rotating machinery, and protective equipment/DPI.

We offer 7 models with different levels of current/voltage featuring two different configurations:

  • 6CP, manual control;
  • 6CB featuring a touchscreen control panel and automatic voltage/current regulation, automatic measurement units, and data acquisition and management functions.

These systems consist of 2 or 3 units, depending on the required power and voltage.

These devices are specified with Partial Discharge values < 10 pC, but can also be ordered with a < 3 pC specification on request for test environments where low levels of Partial Discharge are required.

This portable rugged line of AC high voltage test equipment is ideally suited for use in the field or in the laboratory. The 6CP and 6CB line offer a complete test system in a mobile package. All units use a combination control and regulator enclosure and a separate high voltage section.

The 6CP system is equipped with advanced digital metering, and control and protection devices that are easy to use and provide the operator with all necessary information to safely operate the system.

The 6CB system is equipped with a 7” Full-Color Touch-Screen display with auto-ranging voltage and current meters plus many other additional features.

The Metering Guard Mode allows accurate measurements of the high voltage test specimen leakage current by Model 6CP Model 6CB bypassing stray capacitive currents. The high voltage section consists of a specially designed oil insulated high voltage transformer characterized by use of an isolating cylindrical housing mounted on a rugged steel base. The high voltage output is equipped with a corona free aluminum shielding electrode. The high-quality design and construction is key to low-level partial discharge performance of the 6CP and 6CB line.

The system arrives ready to use with all power and interconnect leads included; the simple setup allows this system to be ready for testing in minutes. The rugged construction and dependability, backed by a long-term warranty make the 6CP and 6CB line an ideal choice for your high voltage testing requirements.

6CP Models – Design & Safety Features

  • 2 or 3 units design
  • Thermal-magnetic circuit breaker
  • Integrated protection interlock system
  • High Voltage ON/OFF pushbuttons with indicators
  • Zero Voltage Interlock System
  • Manual control of output voltage
  • Adjustable overcurrent circuit
  • Slow and fast-acting transient protection on all meters and relays
  • Digital timer with audible alarm
  • Digital, LCD, multi-range metering
  • Emergency off pushbutton (not integrate into 6CP30 and 6CP50 models)
  • Guard mode for accurate current measurements
  • Output overload indicator with reset button
  • All interconnection and power leads are included
  • Provision for leads housing
  • Operation / maintenance manual

6CB Models – Design & Safety Features

  • 7” Full-color touch-screen display
  • Auto-ranging meters for voltage and current
  • Breakdown memory voltmeter
  • Maximum voltage reached memory voltmeter
  • Test duration and dwell timers at test voltage level
  • Zero Voltage Interlock System
  • Tension up/down with motorised system
  • Adjustable voltage rise rate in v/s
  • Adjustable overcurrent trip point
  • Communication port for data acquisition
  • Status bar for system messages
  • Alarm circuit
  • Emergency button Off
  • Circuit protection
  • High Voltage ON/OFF buttons with indicators
  • Automatic voltage control
  • USB data recording via .csv file

Environmental Operating Conditions

  • 10-40°C, indoor/outdoor in fair weather
  • Humidity <95% non-condensing
  • Altitude <3300 ft (1000 meters)
MODEL6CP30/15-3 - 6CB30/15-36CP50/10-3 - 6CB50/10-3
INPUT

Voltage/Current

110-120 V, 16 A

220-240 V, 8 A

110-120 V, 16 A

220-240 V, 8 A

 

Frequency

50/60 Hz

50/60 Hz

OUTPUTVoltage/Current

≈ 0-15 kV, 200 mA 

≈ 0-30 kV, 100 mA 

≈ 0-10 kV, 300 mA 

≈ 0-50 kV, 60 mA 

DUTY CYCLES

5 min ON/15 min OFF

15 min ON/1 hr OFF

1 hr ON/1 hr OFF

3 kVA

2 kVA

1.5 kVA

3 kVA

2 kVA

1.5 kVA

FEATURES

Compensation

Metering Accuracy

Voltmeter Range(s)

Currentmeter Range(s)

Output

50% Inductive Reactive

0.8% Reading + 0.2% of range

0-15 / 30 kV

0-200 µA / 2mA / 20 mA / 200 mA

HV Electrode

50% Inductive Reactive

0.8% Reading + 0.2% of range

0-15 / 50 kV

0-200 µA / 2mA /20 mA / 300 mA

HV Electrode

MODEL6CP100/50-7.5 - 6CB100/50-7.56CP120/60-7.5 - 6CB120/60-7.5
INPUT

Voltage/Current

110-120 V, 30 A

220-240 V, 15 A

110-120 V, 30 A

220-240 V, 15 A

 

Frequency

50/60 Hz

50/60 Hz

OUTPUTVoltage/Current

≈ 0-50 kV, 150 mA 

≈ 0-100 kV, 75 mA 

≈ 0-60 kV, 125 mA 

≈ 0-120 kV, 62.5 mA 

DUTY CYCLES

5 min ON / 15 min OFF

15 min ON / 1 hr OFF

1 hr ON / 1 hr OFF

7.5 kVA

5 kVA

3 kVA

7.5 kVA

5 kVA

3 kVA

FEATURES

Compensation

Metering Accuracy

Voltmeter Range(s)

Currentmeter Range(s)

Output

66% Inductive + Selectable Capacitive Preload

0.8% Reading + 0.2% of range

0-50 / 100 kV

0-200 µA / 2mA / 20 mA / 200 mA

HV Electrode

66% Inductive + Selectable Capacitive Preload

0.8% Reading + 0.2% of range

0-60 / 120 kV

0-200 µA / 2mA /20 mA / 200 mA

HV Electrode

MODEL6CP100/50-10 - 6CB100/50-106CP120/60-10 - 6CB120/60-106CP200/100-10 - 6CB200/100-10
INPUT

Voltage/Current

Frequency

220-240 V, 30 A

50/60 Hz

220-240 V, 30 A

50/60 Hz

220-240 V, 25 A

50/60 Hz

OUTPUTVoltage/Current

≈ 0-50 kV, 200 mA 

≈ 0-100 kV, 100 mA 

≈ 0-60 kV, 166 mA 

≈ 0-120 kV, 83 mA

≈ 0-100 kV, 100 mA 

≈ 0-200 kV, 50 mA

DUTY CYCLES

5 min ON / 15 min OFF

15 min ON / 1 hr OFF

1 hr ON / 1 hr OFF

10 kVA

7.5 kVA

5 kVA

10 kVA

7.5 kVA

5 kVA

10 kVA

7.5 kVA

5 kVA

FEATURES

Compensation

Metering Accuracy

Voltmeter Range(s)

Currentmeter Range(s)

Output

50% Inductive Reactive

0.8% Reading + 0.2% of range

0-50 / 100 kV

0-200 µA / 2mA /20 mA / 200 mA

HV Electrode

50% Inductive Reactive

0.8% Reading + 0.2% of range

0-60 / 120 kV

0-200 µA / 2mA /20 mA / 200 mA

HV Electrode

50% Inductive Reactive

0.8% Reading + 0.2% of range

0-100 / 200 kV

0-200 µA / 2mA /20 mA / 200 mA

HV Electrode

Products Gallery

Service

For any information you can contact us by phone or e-mail:
+39 0471 1800338 -