Neutral Earthing Resistors

Preventing failures in the electrical network

Short circuits between phase and earth can result in irreversible damage to networks and equipment. Earthing resistors from HEINE Resistors limit the fault current that arises between phase and earth due to short circuits.

HEINE offers special, project-specific versions in addition to its standard range of Neutral earthing resistors.  The following technical data is required to design a neutral earthing resistor:

  • Operating voltage
  • Fault current
  • Fault duration (usually 10 seconds)

Our neutral earthing resistors are manufactured as follows:

  • Protection class: IP00 – IP55 (standard: IP23)
  • Stainless-steel housing (1.4301) for outdoor applications or galvanised steel for indoor applications (other materials are available on request)
  • Inclusion of additional components (e.g. vacuum switches, current and voltage transformers, load disconnectors)

Our neutral earthing resistors are used in the following applications:

earth: prevent damage to grid-connected systems, such as transformers or generators

Features

  • Approved and trusted HEINE resistor technology
  • rugged design
  • variety of materials allowing installation at any site: (indoor, outdoor, on-/off-/nearshore)
  • a modular system of standardised enclosures sizes allows short delivery times

Standardised enclosures

Insulation classEnclosure TypeLength [mm]Max. Width [mm]Height [mm]
12 kV

A1

A2

B

C

920

920

1350

1775

1270

1270

1270

1270

1306

1768

1768

1768

24 kV

A1

A2

B

C

1180

1180

1710

2235

1470

1470

1470

1470

1422

1948

1948

1948

36 kV

A1

A2

B

C

1450

1450

2080

2705

1470

1470

1470

1470

1722

2248

2248

2248

Customers

Energy suppliers, transformer and generator manufacturers, renewable energy, Oil & Gas

Nominal Voltageup to 145 kV
Fault Currentup to 10 kA
Insulation Classup to 72.5 kV (higher insulation class available upon request)
Protection ClassIP00 - IP55
Enclosure FeaturesPower Switch
IP00...55Vacuum breaker
Different galvanised and stainless steel gradesOff-load disconnector (manual or motor drive)
Powder-coated according to RAL codesOn-load disconnector (manual or motor drive)
Fan coolingTerminal box with 110 or 220 VDCC
Special equipmentService
Current transformerFactory Acceptance Test (FAT)
Voltage transformerSite Acceptance Test (SAT)
Thermostat control outgoing airCustomer training
NER monitoring systemSpare parts and after-sales service
Surge arrester
Neutral transformer resistor
Applicable Standards
IEC 50386 Bushings up to 1kV and from 250 A to 5kA
IEC 60071 - 1 Insulation coordination - Part 1: Definitions, principles and rules
IEC 60273 Characteristics of indoor and outdoor post insulators above 1kV
IEC 60529 Degrees of protection provided by enclosures (IP Codes)
ANSI/IEEE-Std 32 Standard requirements, terminology and test procedure for NER